If you would prefer to file your propane permit application offline the form can be found here
* A 3.5% PayPal fee Will Be added to your payment
Table 3804.3
Location Of LPG-Gas Containers
CONTAINER CAPACITY (water gallons) |
MINIMUM SEPARATION BETWEEN CONTAINERS AND BUILDINGS, PUBLIC WAYS OR LOT LINES OF ADJOINING PROPERTY THAT CAN BE BUILT UPON |
MINIMUM SEPARATION BETWEEN CONTAINERS (feet) |
|
---|---|---|---|
Moulded or underground containers (feet) |
Above-ground containers (feet) |
||
Less than 125 | 10 | 5 | None |
125 to 250 | 10 | 10 | None |
251 to 500 | 10 | 10 | 3 |
501 to 2,000 | 10 | 25 | 3 |
2,001 to 30,000 | 50 | 50 | 5 |
30,001 to 70,000 | 50 | 75 | (0.25 of sum of diameters of adjacent containers) |
70,001 to 90,000 | 50 | 100 | |
90,001 to 120,00 | 50 | 125 |
For questions concerning a Propane Permit, please call Kent Leavitt, Fire Marshal at (435) 640-4737